For
pipes of outside diameter 60.3 mm and under, a bend test shall
be conducted. A sufficient length of pipe shall stand being
bent cold through 90 around a cylindrical mandrel, the
diameter of which is 12 times the nominal diameter of the
pipe, without developing cracks.
|