Reg. 435, Reg. 436, Reg. 437
SEAMLESS SHELL BOILERS
End Plates
|
The end plates shall comply with Regulation
408 or 412
according as they are dished or flat. When end plates
are mechanically secured and welded to seamless shells
as in earlier figure47 and 48 and the weld are stress-relieved,
the pressure and other limitations specified in respect
of Class II boilers in Regulation
416 shall not apply.
|
Reg. 436
SEAMLESS SHELL BOILERS
Manholes and other opening in the Shells
Reg. 437
SEAMLESS SHELL BOILERS
Mountings, Fittings and Connections (For all types
of Electrode Boilers)
|
Mountings, fittings and connections shall comply with
Regulation 281.
In the case of electrode boilers one means of indicating
water level of the tubular water level gauge-glass type
and one means of feeding the boiler shall suffice and
the Safety Valves shall be of spring loaded type.
If an Electrode boiler is fitted with a magnetic valve,
the said valve will be accepted in lieu of the second
safety valve, provided the source of power supply to
both the valve and the boiler is the same and both are
operated by one single switch.
|
|